Data di Pubblicazione:
2009
Abstract:
This paper reports the performance of clamp-on current transformers under nonsinusoidal conditions. A set of experimental measurements helped to determine the ratio and the phase errors under two conditions: 1) sinusoidal excitation with frequencies from 45 to 1000 Hz and 2) nonsinusoidal excitation using the fundamental frequency and one harmonic, with adjusted phase shift. It was found that ratio and phase errors are affected by the phase angle between the harmonic and the fundamental and the harmonic amplitude. The effects of conductor location in the current transformer's window and of the air-gap width were also investigated. It was concluded that harmonic phase and ratio errors measured in nonsinusoidal conditions can be higher than the ones determined by the frequency response. © 2008 IEEE.
Tipologia CRIS:
01.01 Articolo in rivista
Keywords:
Computerized tomography; Diagnostic radiography; Distributed power generation; Electric current measurement; Electric frequency measurement; Electric instrument transformers; Electric network analysis; Electric power distribution; Electric power systems; Electric power transmission networks; Electric transformers; Errors; Fourier series; Harmonic analysis; Medical imaging; Power electronics; Power transformers; Power transmission; Tomography; Transducers; Circuit faults; Clamp-on current transformers; Computed tomography; Current measurement; Current transformers; Current transformers (CTs); Fault currents; Frequency measurement; Power system harmonics; Frequency response