A novel approach to current transformer characterization in the presence of harmonic distortion
Articolo
Data di Pubblicazione:
2009
Abstract:
The current transformer (CT) performance under distorted waveform conditions is usually characterized by means of the frequency-response test. In this paper, a new way to characterize CTs, closer to real operation conditions, is proposed. The harmonic phase-angle and ratio errors are measured using a nonsinusoidal current composed of fundamental and one harmonic with adjustable phase shift. The new method was tested by determining the performance of two metering class CTs commonly used by the Italian power company. The errors measured using the proposed approach are larger than the ones obtained with the frequency response. This result suggests that the frequency-response approach for the evaluation of CT performance under distorted waveform conditions is not a reliable method. © 2008 IEEE.
Tipologia CRIS:
01.01 Articolo in rivista
Keywords:
Current transformer (CT); Distorted waveforms; Non-sinusoidal currents; Operation conditions; Power companies; Power system harmonics; Ratio errors; Electric current measurement; Electric instrument transformers; Electric power distribution; Electric power transmission networks; Electric transformer testing; Electric utilities; Errors; Harmonic analysis; Harmonic distortion; Piezoelectric transducers; Power electronics; Power transmission; Frequency response