Publication Date:
2003
abstract:
Some experimental data from in field measurements gave us as result a strong lowering of the performances of the
refrigerating units for refrigerated transports during the service time. The question is if this lowering (ageing) is
irreversible (like ageing of the insulation of the boxes) or not.
The ageing of the mechanical refrigerating units is important for the evaluation of the safety coefficients to be used
in coupling the units with the insulated boxes.
We studied an in field measuring system to evaluate the refrigerating power of a unit: the system is based on a pulldown
curve and on the extrapolation of the curve by calculation. The corrections for the evaporating temperatures
are considered.
The measured ageing coefficients seem to be not realistic: we investigated in order to distinguish the physiological
ageing from the lack of maintenance.
A further series of measurements was carried on, taking into considerations seven samples. The measurements were
done on the units without any intervention and after maintenance operations. The results strength the hypothesis that
the larger amount of the measured ageing is due to the lack of maintenance, while the not reversible ageing is some
percents of degree of magnitude.
Iris type:
04.01 Contributo in Atti di convegno
Keywords:
Refrigeration Units; Ageing; Maintenance; Refrigeration Transport