Skip to Main Content (Press Enter)

Logo CNR
  • ×
  • Home
  • People
  • Outputs
  • Organizations
  • Expertise & Skills

UNI-FIND
Logo CNR

|

UNI-FIND

cnr.it
  • ×
  • Home
  • People
  • Outputs
  • Organizations
  • Expertise & Skills
  1. Outputs

Characterization of current transformers in the presence of harmonic distortion

Conference Paper
Publication Date:
2008
abstract:
The CTs performance under distorted conditions are usually characterized by means of the frequency response test. In this paper a new way to characterize CTs, closer to real operative conditions, is proposed. The harmonic phase angle and ratio errors are measured when the CTs are excited with a nonsinusoidal current composed of a fundamental and one harmonic, with adjustable phase shift. The errors measured using the new approach were found larger than the ones obtained with the frequency response. This suggests that frequency response is not a reliable method to evaluate the CT performance under distorted conditions. ©2008 IEEE.
Iris type:
04.01 Contributo in Atti di convegno
Keywords:
Computer networks; Distributed power generation; Electric instrument transformers; Electric transformers; Errors; Instruments; Ketones; Measurement theory; Current transformer; Harmonic distortion; Power system harmonics; Transducers; Frequency response
List of contributors:
DI CARA, Dario
Authors of the University:
DI CARA DARIO
Handle:
https://iris.cnr.it/handle/20.500.14243/209499
Published in:
CONFERENCE PROCEEDINGS - IEEE INSTRUMENTATION/MEASUREMENT TECHNOLOGY CONFERENCE
Series
  • Overview

Overview

URL

http://www.scopus.com/inward/record.url?eid=2-s2.0-51349094340&partnerID=40&md5=8d2ff7a96560107316d997b37a3dda51
  • Use of cookies

Powered by VIVO | Designed by Cineca | 26.5.0.0 | Sorgente dati: PREPROD (Ribaltamento disabilitato)