Data di Pubblicazione:
2007
Abstract:
In this paper, the experimental testing on an advanced solid sorption chiller based on a heat exchanger coated with a compact layer of SWS-1L (CaCl2 in mesoporous silica gel) is presented. The experimental results showed a specific power of 150-200 W/kg of adsorbent and a cycle time of 10-20 min. These values are sensibly better (i.e. one order of magnitude different) than those measured in the same unit working with a SWS- 1L pelletised bed. The cooling COP ranged between 0.15 and 0.3, depending on the operating conditions.
Tipologia CRIS:
01.01 Articolo in rivista
Keywords:
adsorption; air conditioning; SWS; selective water sorbent; coated sorbent bed
Elenco autori:
Vasta, Salvatore; Freni, Angelo; Restuccia, Giovanni
Link alla scheda completa: