This paper presents the energy assessment of a water/water R744 chiller/heat pump,working
according to a transcritical cycle, used for winter heating, summer cooling and tap water
production. The different functions (heating, cooling, hot water) are managed water side.
The analysis of the R744 chiller/heat pump is based on an original simplified method, which
is able to predict the energy performance of the unit based only on its performance data
at the nominal rating conditions. The method was validated against experimental data. A
comparison with a state-of-the-art R410A unit is presented. The monthly analysis shows
that the CO2 unit is very efficient in hot water production, but penalised in heating and cooling
service. The adoption of an ejector in place of the expansion valve makes the CO2 system
reach the same energy consumption as the R410A unit, despite the presence of the water
loop only in the R744 lay-out.
Iris type:
01.01 Articolo in rivista
Keywords:
R744; Heat pump; Air conditioning; Ejector; Water chiller