An optimal hierarchical control scheme for smart generation units: an application to combined steam and electricity generation

Articolo
Data di Pubblicazione:
2020
Abstract:
Optimal management of thermal and energy grids with fluctuating demand and prices requires to orchestrate the generation units (GU) among all their operating modes. A hierarchical approach is proposed to control coupled energy nonlinear systems. The high level hybrid optimization defines the unit commitment, with the optimal transition strategy, and best production profiles. The low level dynamic model predictive control (MPC), receiving the set-points from the upper layer, safely governs the systems consid- ering process constraints. To enhance the overall efficiency of the system, a method to optimal start-up the GU is here presented: a linear parameter varying MPC computes the optimal trajectory in closed-loop by iteratively linearising the system along the previ- ous optimal solution. The introduction of an intermediate equilibrium state as additional decision variable permits the reduction of the optimization horizon,while a terminal cost term steers the system to the target set-point. Simulation results show the effectiveness of the proposed approach.
Tipologia CRIS:
01.01 Articolo in rivista
Keywords:
Hierarchical Control; Model Predictive Control; Optimal Management; Thermal and Energy Grids
Elenco autori:
Spinelli, Stefano; Ballarino, Andrea
Autori di Ateneo:
BALLARINO ANDREA
SPINELLI STEFANO
Link alla scheda completa:
https://iris.cnr.it/handle/20.500.14243/406331
Pubblicato in:
JOURNAL OF PROCESS CONTROL
Journal
  • Dati Generali

Dati Generali

URL

https://www.sciencedirect.com/science/article/pii/S0959152420302808?dgcid=author
  • Utilizzo dei cookie

Realizzato con VIVO | Designed by Cineca | 26.5.0.0 | Sorgente dati: PREPROD (Ribaltamento disabilitato)