The European development of a full scale switching unit for the ITER switching and discharging networks

Academic Article
Publication Date:
2005
abstract:
The European Fusion Programme included since the mid-1990s, the development of a full scale, full rating current commutating unit (CCU) to be used as a centre-piece of the ITER magnet protective circuits. The CCU is mainly composed of a by-pass switch (BPS) in parallel to a vacuum circuit breaker (VCB). Both full scale switches were subjected to extensive testing in conditions simulating the actual ITER operation. The operation in absence of the saturable reactor series connected in the ITER reference design was successfully assessed. Interruption tests at low current and full counter-pulse capacitor voltage, were also satisfactorily performed. The tests included an extensive and novel characterisation of the interrupting capability of the vacuum circuit breaker in the presence of an external magnetic field as in the actual location of installation in ITER.
Iris type:
01.01 Articolo in rivista
Keywords:
DC circuit breakers; ITER; Superconductive magnet protection
List of contributors:
DE LORENZI, Antonio; Piovan, Roberto
Handle:
https://iris.cnr.it/handle/20.500.14243/42405
Published in:
FUSION ENGINEERING AND DESIGN